This cable supports security, audio, BMS, RS232/RS485 and fire alarm systems, usable in dry or humid areas, with twisted pairs and full foil shielding for interference reduction.
| Component | Technical Detail |
|---|---|
| Conductor | Flexible class 5 stranded tinned copper conductor intensies anti-oxidative and anti-corrosive properties |
| Insulation | Polyethylene (PE) compound, twisted in pair |
| Overall screen | Aluminium foil and tinned copper braid |
| Drain wire | Tinned copper drain wire |
| Outer sheath | PVC/LSZH. Color: Grey/Orange/Black |
| Specification | Value/Condition |
|---|---|
| Rated voltage |
300/500V – Control & instrumentation applications (Optional: 600/1000V) 30V – Analog/digital transmission |
| Test voltage | 1500V |
| Rated temperature | -30°C to +70°C |
| Conductor resistance (max) @20°C (Ω/km) |
According to IEC 60228 18 AWG: 23.5; 20 AWG: 35.8; 22 AWG: 57.4; 24 AWG: 90.9 |
| Insulation resistance | > 2 GΩ x km |
| Impedance | 120 Ω |
| Recommended current (max) @25°C (Amps) | 18 AWG: 7.2; 20 AWG: 4.9; 22 AWG: 2.9; 24 AWG: 2.1 |
| Smoke density | IEC 61034-2 (LSZH sheath) |
| Halogen free | IEC 60754-1 (LSZH sheath) |
| Flame retardant | IEC 60332-1 |
| Standard & Approval | ROHS, UL |
| UL standard | UL2092, UL2919,... |
| Minimum bending radius | 8 x OD (static) |
@ Copyright belongs to Chau Duy Phat